As the penetration of wind power into power grids increases,higher demands are made on the stability and protection of power systems.Unlike traditional synchronous generators,wind turbines are different on the short-circuit and impedance characteristics,thus some problems exist in pilot protections of transmission lines connecting wind farms.When a single-phase fault occurs on a transmission line,the phase selector based on current-difference sudden-change may mistake the single-phase fault for a phase-to-phase fault.This paper studies the impedance characteristics of an asynchronous wind generator,and analyzes the behavior of a fault phase selector under different conditions.Then,the paper explains that inequality between positive and negative branch coefficients is the cause for the mal-operation of the fault phase selector.Finally,some simulations are done in MATLAB to validate analysis results.